1–11a theory of operation – OnLine Power PBC I User Manual

Page 18

Advertising
background image

1–11A Theory of Operation

Functional Block Diagram shows the power path through the PBC, See Illustration 1-6A
for international models.

Input Stage

•

The utility company’s power sinewave enters the system by way of TB 1.

•

The CB-1 is a 2-pole breaker shown as CB-1A & CB-1B for international models.

•

The Joslyn, TVSS, supply input surge protection, is after CB-1A and CB-1B for international models.

•

From the Joslyn, TVSS at TB4 is the EMI filter, network attenuation of any power line noise occurs.

•

On exiting the input filter, the AC voltage enters the Autotransformer and is stepped down to 120 VAC
required by A1 PCBA UPS Inverter Module.


The Power Splits Into Two ( 2 ) Directions

•

Quick Battery Charger, A7 PCBA reduces the recharge time after the batteries after a power outage.

•

The Power Conditioning UPS Module, A1 PCBA.


Power Conditioning Stage

• The Power Conditioning Module has 6 sections and their functions are follows:

•

The power from the on board Battery Charger supplies a float charge to the Standby Reserve Battery
System.

•

The Emergency Bypass line connects the input to output by way of on board Emergency
Bypass Switch.

•

The Power Rectifier section provides DC Voltage to the DC Chopper.

•

The ± DC Choppers change DC Voltage from the power Rectifier and the batteries to a pulse Voltage for
the DC/AC Inverter.

•

The DC/AC Inverter supplies a Pulse Width Modulation Output through the Bypass Switch to the Output
Filter.

•

The Output Filter changes the Pulse Width Modulation to a clean sinewave and to the Output Isolation
Transformer.

Power Output Stage

• The Output Filter connects to the 2 Fans, B 2 and B 3, providing constant airflow to cool the Electronic

Tray components, and to T 2, Output Isolation Transformer.

• The Output Isolation Transformer, T2, connects to CB-3 A and CB-3B, the Output Circuit Breaker and

provides voltage to the terminals of TB-2 and the load.

Power Outage Stage

If there is a power outage; the Standby Reserve Battery System supplies the power through CB-2
to the UPS. The Battery DC voltage enters the ± DC Chopper, DC / AC Inverter, Bypass Switch
and to the Output Filter, Output Transformer, CB 3, to TB 2, and the load.






11