SECTION 2 – PREINSTALLATION

2-1 Location Considerations

•

Provide an operating environment that meets the following conditions:

Ambient Temperature is 0

O

C to 40

O

C ( 32

O

F to 104

O

F )

Relative Humidity is 10 to 95 % Non-Condensing.

2-2 Positioning

•

Allow at least a minimum of 3 inches to the rear for airflow. The PBC is air cool by convection.

•

Door shall have full 110 degrees open clearance, and have 5 feet clearance in front for basket or platform.

DANGER

•

Inspection Safety Zone of Tray is 6 inches. Pass that point the tray needs support, due to weight.

•

The Electronic Tray weight varies by model and is approximately 52 to 57 lbs.

•

The Battery Tray weight varies by model and is approximately 200 to 290 lbs.

•

The PBC varies by model and is approximately 365 to 455 lbs.

2-3 Mechanical Overall Dimensions and Weight

Model

Rating

Maximum Cabinet Dimensions

Maximum

Weight

Lifting Hole

Diameter

650 W

19.5” W x 20” H x 20.75” D

365 lbs.

0.875

650 W

# 1 20.25” W x 26” H x 20.75” D

375 lbs.

0.875


LU0.4xxx

&

LU0.7xxx

650 W

# 2 20.25” W x 27.5” H x 20.75” D

385 lbs.

0.875

1300 W

19.5” W x 20” H x 20.75” D

455 lbs.

0.875

1300 W

# 1 20.25” W x 26” H x 20.75” D

465 lbs.

0.875

LU1.5XXX

1300 W

# 2 20.25” W x 27.5” H x 20.75” D

475 lbs.

0.875

Note: # 1 PBC Height with Lifting & Pole Mounting Plates.

# 2 PBC Height with Pad mounting Plates and Lifting Plates.


NOTE: 1300W models IS de-rated to 400W UPS when used in; Sealed cabinet for environmental protection

application, units have no louvers or when a sealing kit option is add to a louver unit.


NO! Change in the weight of sealed cabinets units. Add 10 pounds to weight for Sealing Kit.

2-4 Site Planning Specifications

Nominal

Input

Voltage

220 VAC

230 VAC

120 VAC

220 VAC

240 VAC

Input Voltage

Range

168 -- 264

168 -- 264

85 -- 132

168 -- 264

168 -- 264

Max. Input

Voltage

264 VAC

264 VAC

132 VAC

264 VAC

264 VAC

Input Frequency

*

50 Hz

50 Hz

60 Hz

60 Hz

60 Hz

Output

Frequency

50 Hz

± 0.5 %

50 Hz

± 0.5 %

60 Hz

± 0.5 %

60 Hz

± 0.5 %

60 Hz

± 0.5 %

Output Voltage

230 VAC

±3%

230 VAC

±3%

120 VAC

± 3%

240 VAC

±3%

240VAC

± 3%

* Factory pre-set. Can be selected for either 50 or 60 Hz.

2-5 Site Detail Electrical Specifications

• See page 7, Section 1-8 and 1-9 for more details.