Slaved Zone Damper Wiring

For large zones it may be necessary to have more than one air damper
controlled by a VAV/Zone controller and its associated space sensor.
The Orion system allows for connecting up to two additional slaved
zone dampers to the master VAV/Zone controller. Slaving is not avail-
able for pressure independent damper applications.

Note: Each slaved actuator is considered a modular device rated

at 6 VA each. This 6 VA load must be included in the
transformer sizing and branch circuit calculations for the
Power/Comm board. See the previous section regarding
transformer sizing of the Power/Comm board for com-
plete information.

Two Slave Wiring Adapters (OE267) consisting of a slave wiring inter-
face card and modular cable are supplied with the OE523 Round Slaved
Zone Damper, OE738 Slaved VAV/Zone Rectangular Damper Kit and
the OE282-03 Slaved VAV/Zone Damper Kit. These are required when
attaching slave actuator(s) to the master zone damper. One slave wiring
interface card should be mounted in the control enclosure of the master
VAV/Zone controller. It is mounted by fastening the plastic snap-track
to the control enclosure with sheet metal screws provided. The other
card is mounted in the control enclosure of the slaved zone damper.
Fasten it in the control enclosure of the slaved zone damper as was
previously done with the master VAV/Zone controller. Run 24 AWG
minimum wire between the slave wiring interface cards. Connect modu-
lar cables to the slave wiring interface cards and to the zone actuators
as shown. See Figure 6 for complete wiring details.

SLAVED- ZONE ACTUATOR #2

(WHEN USED)

SLAVED-ZONE ACTUATOR #1

ZONE ACTUATOR #1

(MASTER)

MODULAR CABLE

MODULAR CABLE

MODULAR

CABLE

MODULAR

CABLE

1

1

0

0

1

0

(PL101824) BYPASS AND

SLAVE INTERFACE CARD

(PL101824) BYPASS AND

SLAVE INTERFACE CARD

(PL101824) BYPASS AND

SLAVE INTERFACE CARD

HZ000095

HZ000095

HZ000095

HZ000095

OE282

OE282

OE282

(OE324) ZONE CONTROLLER BOARD

FROM

ZONE

CONTROLLER

BYP

ASS

AND

SLA

VE

INTERF

ACE

YS101824

T

O

ACTUA

TO

R

OPEN

CLOSE

FDBK

OPEN

GND

GND

PJ1

PJ2

LD2

LD1

OPEN

CLOSE

CLOSE

TB1

TB2

FROM

ZONE

CONTROLLER

BYP

ASS

AND

SLA

VE

INTERF

ACE

YS101824

T

O

ACTUA

TO

R

OPEN

CLOSE

FDBK

OPEN

GND

GND

PJ1

PJ2

LD2

LD1

OPEN

CLOSE

CLOSE

TB1

TB2

NOT USED FOR
THIS APPLICATION

NOT USED FOR
THIS APPLICATION

FROM

ZONE

CONTROLLER

BYP

ASS

AND

SLA

VE
INTERF

ACE

YS101824

T

O

ACTUA

TO
R

OPEN

CLOSE

FDBK

OPEN

GND

GND

PJ1

PJ2

LD2

LD1

OPEN

CLOSE

CLOSE

TB1

TB2

OE520, OE736, OE742

OE267

PJ2

PJ1

ACTUATOR

EXPANSION

OE523,

OE738,

OE282-03

OE523,

OE738,

OE282-03

Figure 6: Slaved Zone Wiring & Connection Diagram

Controller Installation & Wiring

Advertising