Technical Guide

HB Mini Controller

14

High Pressure Switch

HPS

OPEN

Line #2 displays the current status of the High Pressure Switch. It
will only display “CLOSED” when Cooling Relay #1 relay is active
and the High Pressure Switch is operating correctly.

Cooling Module Setpoint Screens

The Cooling Module Setpoints Screens are accessed by navigating to
the Cooling Module screen and then pressing the ENTER key. The fol-
lowing screen will then appear.

Status

Setpoints

Press the down SELECT arrow key until “Setpoints” is on the top line
of the screen and then press the ENTER key. Press the down SELECT
arrow key or up SELECT arrow key to move forward or backward
through the Cooling Module Setpoint screens.

Please see the Appendix section in the back of this manual for Tables
listing the minimum, maximum and default setpoints for all of the
setpoint screens.

Cooling Stages Quantity

Cool Stages

X

Adjust the quantity of Cooling Stages or Steps of Cooling and then
press the ENTER key.

Outdoor Air Temperature Cooling Lockout

OAT Cool Lockout

XXX F

Adjust the Outdoor Air Temperature Cooling Lockout and then press
the ENTER key.

Cooling Minimum Off Time

Cool Min Off

XXX Sec

Adjust the desired Cooling Minimum Off Time and then press the
ENTER key.

Cooling Minimum On Time

Cool Min On

XXX Sec

Adjust the desired Cooling Minimum On Time and then press the EN-
TER key.

Cooling Stage Up Delay

Cool Stage Up

XXX Sec

Adjust the desired Cooling Stage Up Delay time and then press the
ENTER key.

Cooling Stage Down Delay

Cool Stage Down

XXX Sec

Adjust the desired Cooling Stage Down Delay time and then press the
ENTER key.

Low Pressure Switch Delay

LPS Delay

XXX Sec

The Low Pressure Switch Delay time is a factory setting and should not
be changed unless authorized to do so by WattMaster or AAON

®

Tech-

nical Support.

Low Pressure Switch Safety Delay

LPS Safety

XX Sec

The Low Pressure Switch Safety Delay time is a factory setting and
should not be changed unless authorized to do so by WattMaster or
AAON

®

Technical Support.

LPS Maximum Trips

LPS Max trips

XX

The Low Pressure Switch Max Trips is a factory setting and should not
be changed unless authorized to do so by WattMaster or AAON

®

Tech-

nical Support.

Programming With The HB Service Tool