Hb mini controller technical guide 15 – Orion System HB Mini User Manual

Page 15

Advertising
background image

HB Mini Controller

Technical Guide

15

Cooling Fan Off Delay

Cool Fan Off Dly

XXX Sec

The Cooling Fan Off Delay is a factory setting and should not be
changed unless authorized to do so by WattMaster or AAON

®

Techni-

cal Support.

Auto Stage Up Time

Auto Stage Up

XXX Sec

The Auto Stage Up Time can be adjusted on this screen when you are
using a single-stage thermostat with a multi-stage HB unit.

Heating Module Status Screens

The Heating Module Status Screens are accessed by navigating to the
Heating Module screen and pressing the ENTER key. The following
screen will then appear.

Status

Setpoints

Select “Status” by pressing the ENTER key. Press the up or down SE-
LECT arrow key to move forward or backward through the Heating
Module Status screens.

Heating Stage 1 Energized

W1-Active

NO

Line #2 displays “YES” if there is a 24 VAC signal on HB Mini Con-
troller terminal “W1”.

Heating Stage 2 Energized

W2-Active

NO

Line #2 displays “YES” if there is a 24 VAC signal on HB Mini Con-
troller terminal “W2”.

Heating Stage 3 Energized

W3-Active

NO

Line #2 displays “YES” if there is a 24 VAC signal on HB Mini Con-
troller terminal “W3”.

Fan Status

Fan Status

Fan Off

Line #2 displays the current Supply Fan Status. If the Supply Fan is
on, line #2 displays either “Fan Low Speed” or “Fan High Speed”.

Heating Relay #1

Heat 1 Relay

OFF

Line #2 displays “ON” if Heating Relay #1 is active.

Heating Relay #2

Heat 2 Relay

OFF

Line #2 displays “ON” if Heating Relay #2 is active.

Heating Relay #3

Heat 3 Relay

OFF

Line #2 displays “ON” if Heating Relay #3 is active.

Heat Safety Monitor

HSM

CLOSED

Line #2 displays “OPEN” anytime the Heat Safety Monitor is open.