Hb mini controller technical guide 17 – Orion System HB Mini User Manual

Page 17

Advertising
background image

HB Mini Controller

Technical Guide

17

HSM Lockout

HSM Lockout

NO

Line #2 displays “YES” when the Heat Safety Monitor has tripped more
than the HSM Max Trips setpoint.

HPS Fault

HPS Fault

NO

Line #2 displays “YES” when the High Pressure Switch is open and
a Cooling Relay is active.

LPS Lockout

LPS Lockout

NO

Line #2 displays “YES” when the Low Pressure Switch has tripped
more than the LPS Max Trips setpoint.

Bad OAT Sensor

Bad OAT

NO

Line #2 displays “YES” when the Outdoor Air Temperature Sensor is
bad or missing.

OAT Cooling Lockout

OAT Cool Lockout

NO

Line #2 displays “YES” if the Outdoor Air Temperature is below the
Cooling Lockout Temperature setpoint.

OAT Heating Lockout

OAT Heat Lockout

NO

Line #2 displays “YES” if the Outdoor Air Temperature is above the
Heating Lockout Temperature setpoint.

Clogged Filter

Clogged Filter

NO

Line #2 displays “YES” if there is a 24 VAC signal on the Clogged
Filter Input.

HVAC Test Module Screens

The HVAC Test Module screens are accessed by navigating to the HVAC
Test Module screen and pressing the ENTER key. After pressing EN-
TER the following screen will then appear.

Force Time Limit

Force Time Limit

XXX Min

Adjust the desired time needed for forcing the HB Mini Controller
into an HVAC Test Mode and then press the ENTER key.

Force Relays

Force Relays

NO

Select “YES” to enable Relay Force Mode and then press the ENTER
key.

High Speed Fan Relay Force

HSpd Fan Relay

OFF

Select “YES” to activate the High Speed Supply Fan Relay and then
press the ENTER key.

Low Speed Fan Relay Force

LSpd Fan Relay

OFF

Select “YES” to activate the Low Speed Supply Fan Relay and then
press the ENTER key.