2 set o.c.p, 4 timing output, 1 enter/exit timer status – OWON ODP Series User Manual

Page 23

Advertising
background image

5.Front Panel Operation

18

"ON" or "OFF", the O.V.P in current mode and status is enabled or disabled.

Note:
In Plus-minus mode, the O.V.P status of Positive and Negative will remain consistent, you
can set either of them. The O.V.P value can be set separately.

(3) Use the numeric keys to enter the O.V.P value in current mode and status. The

maximum in Independent, Parallel, Plus-minus mode is 31.5V, the maximum in Series

mode is 63V. Press the

key to confirm.

5.3.2 Set O.C.P

(1) Enter the O.C.P setting menu:

Independent Mode

Press the System key, enter [System

CH1 (CH2) O.C.P].

Parallel, Series Mode

Press the System key, in normal status, enter [System

O.C.P];

in timer status, enter [System

Pro Set O.C.P].

Plus-minus Mode

Press the System key, enter [System

Positive (Negative) O.C.P].

(2) A setting box pops up, press the

▲ / ▼ key to switch the state of the O.C.P between

"ON" or "OFF", the O.C.P in current mode and status is enabled or disabled.

Note:
In Plus-minus mode, the O.C.P status of Positive and Negative will remain consistent, you
can set either of them. The O.C.P value can be set separately.

(3) Use the numeric keys to enter the O.C.P value in current mode and status. The

maximum in Independent, Series and Plus-minus mode is 3.15A, the maximum in

Parallel mode is 6.3A. Press the

key to confirm.

5.4 Timing Output

The timing output function can preset up to 100 groups of timing parameters. When you
turn on the timing output, the instrument will output the pre-specified voltage, current in
pre-specified time.
You can set special O.V.P/O.C.P for timer status; see "Over Voltage/Current Protection"
for more details.

5.4.1 Enter/Exit Timer Status

Press Timer to enter/exit timer status.

The

icon identifies the system is in timer status.

Advertising