CAUTION: For propane/LP

gas, make sure external regula-

tor has been installed between

propane/LP supply and heater.

See guidelines under Connect-

ing to Gas Supply, page 11.

PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1. Disconnect appliance with its appliance main gas

valve (control valve) and equipment shutoff valve

from gas supply piping system. Pressures in excess

of 1/2 psig will damage heater regulator.

2. Cap off open end of gas pipe where equipment

shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

4. Check all joints of gas supply piping system.

Apply a noncorrosive leak detection fluid to

all joints. Bubbles forming show a leak.

5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff

valve to gas supply. Check reconnected fit-

tings for leaks.

Test Pressures Equal To or Less Than 1/2
PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 16).
2. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

3. Check all joints from gas meter for natural gas

(see Figure 17) or propane/LP supply tank for

propane/LP gas, to equipment shutoff valve (see

Figure 18). Apply a noncorrosive leak detection

fluid to all joints. Bubbles forming show a leak.

4. Correct all leaks at once.

Figure 16 - Equipment Shutoff Valve

Equipment
Shutoff
Valve

Figure 18 - Checking Gas Joints for

Propane/LP Gas

Propane/LP
Supply Tank

Thermostat
Gas Valve

Figure 17 - Checking Gas Joints for

Natural Gas

Equipment Shutoff Valve

Gas
Meter

Thermostat Gas
Valve

Open

Closed

Equipment Shutoff Valve

PRESSURE TESTING HEATER GAS
CONNECTIONS

1. Open equipment shutoff valve (see Figure 16).
2. For natural gas open main gas valve located

on or near gas meter. For propane/LP gas open

propane/LP supply tank valve.

3. Make sure control knob of heater is in the OFF

position.

4. Check all joints from equipment shutoff valve

to thermostat gas valve (see Figure 17 or 18).

Apply a noncorrosive leak detection fluid to all

joints. Bubbles forming show a leak.

5. Correct all leaks at once.
6. Light heater (see Operating Heater, page 14).

Check all other internal joints for leaks.

7. Turn off heater (see To Turn Off Gas to Appli-

ance

, page 15).

8. Replace front panel.