REMKO Multi-talent Plus User Manual

Page 17

Advertising
background image

Heating circuit 1/2-continued

Designation

Value range

Factory setting

Description

T-supply const T

10°C-110°C

35.0°C

The T-supply const function must be activated (see specialist

heating circuit 1/2

HC function).

Setting the desired supply temperature with which the selected
heating circuit is operated during the heating period.

T-supply const N

10°C-110°C

10.0°C

The T-supply const function must be activated (see specialist

heating circuit 1/2

HC function).

Setting the desired supply temperature with which the
selected heating circuit is operated during the reduction
period.

Room impact

Off

00-20

Off

Only in the absence of an analogue room device (FBR).

The WE temperature is increased in the amount of the value
set here if the desired room temperature (T-room target) is
undercut by 1K (room sensor impact).

Heating curve ad-

aptation

On/Off

Off

Automatic regulation of the heating curve
(Heating curve adaptation).

Start-up requirements:
• Outdoor temperature < 8°C
• Operating mode is automatic 1/2
• Duration of the reduction phase at least 6 hours

The current room temperature is measured at the beginning
of the reduction period. This temperature is applied in
the following 4 hours as the target value for the room
regulation. The heating curve is calculated from the values
captured in this time period by the regulator for the supply
and outdoor temperatures.

The setting remains on until the adaptation has been
completed successfully and was not interrupted (e.g. by
a demand for hot water from an external heating circuit).

The controller's water heating and the warm up
optimisation are blocked during the adaptation.

Warm up opt

Off

T-room

T-external

Off

Automatic bringing forward of the heating period start
(warm up optimisation).

Dependent on the weather (T-external) or the current
room temperature (T-room, only in the absence of an
analogue room device (FBR), heating is started up early
enough so that at the beginning of the set heating period,
the temperature in the living area (see time programme

heating circuit 1/2 prog 1/2) just reaches the set room

target temperature (T-room target).

The warm up optimisation is only carried out if the reduction
time for the heating circuit is at least 6 hours.

Level 4 - USER - Description of parameters and settings - continued

17