Remko heat pump manager – REMKO Multi-talent Plus User Manual

Page 38

Advertising
background image

REMKO Heat Pump Manager

Heating circuit 1/2

Designation

Value range

Factory setting

Description

HC function

Standard

T-supply const

Swimming pool

(HC2)

WW(HC2)

Return(HC2)

Standard

Setting the function for the respective heating circuit.

Standard (weather managed target temperature regulation
using heating curves).

T-supply const (control in accordance with fixed supply
temperatures).
During heating periods (see time programme

heating

circuit 1/2 prog 1/2) the heating circuit is operated with the
set fixed supply temperature T-supply const T, during reduc-
tion periods correspondingly with the set fixed supply tem-
perature T-supply const N (see user

heating circuit 1/2

T-supply const T/N).

Swimming pool (swimming pool regulation, only for heat-
ing circuit 2).

WW (hot water circuit).
The supply sensor for heating circuit 2 is located in the hot
water tank [sensor 05].
The target value for the hot water temperature can be en-
tered under user

hot water

T-WW target 1/2/3.

The heating programme for the heating circuit functions as
an enabling programme for the tank.
During the reduction period, the tank's target temperature is
set to 10°C.
The WE controller's hot water priority function can be used
(see specialist

hot water

PPL).

Return (return riser above mixer, only for heating circuit 2)
- not relevant for REMKO.
The supply sensor for the heating circuit is used as the return
sensor for the WE [sensor 11/05].
The mixer regulates 24h based on the heating circuit's set
value, Min T-supply.

Installation note:

Mixer Open: The WE's supply is fed into the return (return
riser) (circulation must be ensured by the WE).
Mixer Closed: Return for the heating circuits is piped.

The parameters for this level change in accordance with the function selected for the heating circuit.
Depending on the heating circuit, the values that can be adjusted here can vary.

Level 4 - SPECIALIST - Description of parameters and settings - continued

38