REMKO Heat Pump Manager

Hot water

Designation

Value range

Factory setting

Description

Charge pump lock

On/Off

Off

Activating the 3-way switch valve for process hot water or
alternatively a charge pump for process hot water.


The 3-way switch valve only switches if the temperature
[sensor 08] exceeds the tank temperature [sensor 06] by 5K
(= ON).

Back to position heating if the temperature of the F-8 sensor
falls below the tank temperature. This prevents cooling of
the tank at the beginning of the water heating.

PPL

PartialPriority WW

On/Off

PPL all

PPL all

WW (partial priority WW).
Heating circuits are locked for water heating. The mixers
close and the heating circuit pumps switch off.
The mixer circuits are enabled again if the WE reaches the
hot water target temperature (see user

hot water

T-WW target)+WE target increase (T-WE WE).
The mixer circuits lock again if the WE temperature [sensor
08] falls below the enable temperature by the amount of the
switching hysteresis (hysteresis WW).

ON (pump parallel operation).
Only the direct heating circuits are locked for water heating.
The mixer circuits continue to be heated
(the water heating is extended with this function).

Off (hot water priority mode).
Heating circuits are locked for water heating. The mixers
close and the heating circuit pumps switch off.

PPL all (pump parallel operation also for the direct heating
circuit).
All heating circuits continue to be heated during water heat-
ing.
If the temperature exceeds the maximum supply tempera-
ture (see specialist

heating circuit 1/2

Max T-supply)

by 8K, the heating circuit pump for this circuit will shut off
(overheating protection).
The heating circuit pump switches on again if the tempera-
ture falls below the temperature (Max T-supply+5K).

T-WE WW

0.0K-50.0K

10.0K

Setting the additive temperature for the heating appliance
during water heating (target increase in WW mode).

The target temperature for heating appliances during
water heating is arrived at by adding the hot water target
temperature (see user

hot water

T-WW target) to

the temperature set here.

The WE must be operated at an increased temperature
during water heating so that the hot water temperature in
the tank can be reached over the heat exchanger.

Level 4 - SPECIALIST - Description of parameters and settings - continued

36