REMKO Multi-talent Plus User Manual

Page 25

Advertising
background image

Configuration - continued

Designation

Value range

Factory setting

Description

eBUS supply

On/Off

Off

Activating the eBUS supply in accordance with the con-
nected devices.

System selection

----/01-12

01

With this setting, additional values at the configuration level

can be brought forward (selecting the basic functions).

The display value here is always "00".

• 01 = Basic hydraulics for the functions “Heating and hot
water”, single energy-source mode, 1 supplemental electric
heating, bivalence point -5°C

• 02 = only heating version, single energy-source mode,

2 levels for supplemental electric heating, bivalence point -5°C.

• 03 = only heating version, bivalent mode, boiler + option

for 1 supplemental electric heating, bivalence point -3°C.

• 04 = only heating version, bivalent mode, solid fuel boiler

+ option for supplemental electric

Supplemental heating, bivalence point -3°C.

• 05 = only heating version, single energy-source mode,

1 supplemental electric heating, solar system, bivalence point -5°C.

• 06 = only heating/cooling version, single energy-source

mode, 1 supplemental electric heating, bivalence point -5°C.

• 07 = only heating/cooling version, single energy-source

mode, 1 supplemental electric heating, solar system,

bivalence point -5°C.

• 08 = only heating version, single energy-source mode,

2 levels for supplemental electric heating, solar system,

bivalence point -5°C.

• 09 = only heating version, bivalent mode + option for 1

supplemental electric heating, solar system, bivalence point -3°C.

• 10 = only heating/cooling version, bivalent mode,

bivalence point -3°C

• 11 = heating/cooling version, bivalent mode, solar system,

bivalence point -3°C

• 12 = heating/cooling version, bivalent mode with solid fuel +

option for 1 supplemental electric heating, bivalence point -3°C

There is no change for "----".

Regulator type

00-06

06

Setting the regulation type for the system.
• 00 = No heating appliance (mixer expansion).
• 01 = Single stage WE (switching).
• 02 = Single stage (modulating).
• 03 = Two stage WE (switching).
• 04 = Two individual WE (switching).
• 05 = Multi-level switching (cascade over BUS).
• 06 = Multi-level modulating (cascade over BUS).

WE 1 type

(Output A6

enable or demand

heat pump)

00-09

07

• 00 = Relay has no function.
• 01 = Switch on WE.
• 07 = Switch on heat pump.
• 08 = Switch on cooling 1.
• 09 = Switch on cooling 2.

Level 4 - SPECIALIST - Description of parameters and settings - continued

25

Advertising