VENT TERMINATION CLEARANCES

The final position of your fireplace depends on

the location of the vent termination in relation to

the clearances that must be observed as shown in

Figure 5 on page 6.
The vent system serves as the “chimney” as well

as the combustion air supply (air intake). The

horizontal run must have a rise of 1/4" (.6 cm) for

every 12" (30.48 cm) of horizontal run towards the

termination. The maximum horizontal run depends

on the vertical rise from the fireplace adapter collar

to the vent termination (see table below).

VERTICAL

HORIZONTAL

0

to

1 ft (30.48 cm)

1 ft (30.48 cm)

to

4 ft (121.92 cm)

2 ft (60.96 cm)

to

8 ft (243.84 cm)

3 ft (91.44 cm)

to

12 ft (365.76 cm)

4 ft (121.92 cm)

to

16 ft (487.68 cm)

5 ft (152.40 cm)

to

15 ft (457.20 cm)

6 ft (182.88 cm)

to

14 ft (426.72 cm)

7 ft (213.36 cm)

to

13 ft (396.24 cm)

8 ft (243.84 cm)

to

12 ft (365.76 cm)

WARNING: Never allow the

vent to run downward as this

may cause excessive tempera-

tures which could cause a fire.

WARNING: Horizontal sec-

tions of this vent system require

a minimum clearance of 2" from

the top of the pipe and 1" mini-

mum to the sides and bottom.

Vertical sections of this system

require a minimum of 1" clear-

ance to combustible materials

on all sides of the pipe.

PRE-INSTALLATION

PREPARATION

Continued

CD32M

CD36M-A CD42M-A

A

32

3

/

8

"

36

1

/

8

"

40

1

/

8

"

B

34

5

/

8

"

41

1

/

4

"

48

1

/

4

"

C

19"

23

1

/

2

"

25

5

/

8

"

Figure 3 - Framing Dimension

Figure 4 - Corner Installation

A

B

E

F

G

H

D

C

Nailing Tabs

B

A

C

CD32M

CD36M-A

CD42M-A

A

28

1

/

2

"

35

3

/

4

"

41

5

/

8

"

B

13

5

/

8

"

15"

21

5

/

8

"

C

39

3

/

8

"

49

5

/

8

"

58

1

/

2

"

D

9

1

/

2

"

10

3

/

8

"

13

1

/

2

"

E

9

7

/

8

"

13

3

/

4

"

16

3

/

4

"

F

34

1

/

2

"

41

1

/

8

"

48"

G

35

1

/

2

"

42

1

/

8

"

48

1

/

4

"

H

54

3

/

8

"

68

1

/

4

"

81

1

/

2

"

FRAMING

Once the final location has been determined, ob-

serving height clearances for vent termination, you

may construct framing using dimensions shown in

Figures 3 and 4, depending on your installation.
If the appliance is to be installed directly on carpet-

ing, tile (other than ceramic) or any combustible

material other than wood flooring, the appliance

must be installed on a metal or wood panel extend-

ing the full width and depth of the appliance.