Westermo TD-36 User Manual

Page 40

Advertising
background image

40

6618-2202

TD-36 485 sending text message with SMS by usage of Generic I/O
Configure a TD-36 485 to send different SMS depending
on the I/O input pulse train.

AT&F

Set the unit to factory default

AT&W

Store default settings

AT*WIOP=5,10,2,3,0

Set I/O params
Min pulse time = 50 ms (5)
Max pulse time = 100 ms (10)
Trig type = Pulsed trigged (2)
Pulse trig type = POS, pos edge (3)
Output type = No output (0)

AT*WIOL=2,2,0,0,0,”num1”,”text1”,”
providernum1”,1,”password1”

Entry = 2 (2)
Service = SMS (2)
Retry = NO (0)
Timeout = 0
Priority = 0
Data 1 = SMS receiver number (num1)
Data 2 = SMS text (text1)
Data 3 = SMS provider number (providernum1)
Data 4 = SMS protocol type UDP (1)
Data 5 = Password if required by provider (password1)

AT*WIOL=3,2,0,0,0,”num2”,”text2”,”
providernum2”,1,”password2”

Entry = 3 (3)
Service = SMS (2)
Retry = NO (0)
Timeout = 0
Priority = 0
Data 1 = SMS receiver number (num2)
Data 2 = SMS text (text2)
Data 3 = SMS provider number (providernum2)
Data 4 = SMS protocol UDP (1)
Data 5 = Password if required by provider (password2)

Configure the TD-36 485

5 – 48 V

Trigging SMS no 2

Trigging SMS no 3

GSM

Network

PSTN

Network