Cooling system, Esd prevention – H3C Technologies H3C SR6600 User Manual

Page 12

Advertising
background image

4

Table 4 Dust concentration limit in the equipment room

Substance

Concentration limit (particles/cu m)

Dust particles

≤ 3 x 10

4

(No visible dust on desk in three days)

NOTE:

Dust particle diameter ≥ 5 μm

The equipment room must also meet strict limits on salts, acids, and sulfides to eliminate corrosion and

premature aging of components, as shown in

Table 5

.

Table 5 Harmful gas limits in an equipment room

Gas Max.

(mg/m

3

)

SO

2

0.2

H

2

S 0.006

NH

3

0.05

Cl

2

0.01

Cooling system

The H3C SR6602 router adopts left to right airflow for heat dissipation.

Figure 3 SR6602 airflow

•

Make sure there is enough space (greater than 10 cm (3.94 in)) around the air intake and outlet
vents on the router for good ventilation.

•

Make sure the installation site has a good cooling system.

ESD prevention

To prevent electrostatic discharge (ESD), note the following guidelines:

•

Make sure that the router and the floor are well grounded.

•

Take dust-proof measures for the equipment room.

•

Maintain the humidity and temperature at a proper level.

•

Always wear an ESD-preventive wrist strap when touching a circuit board or transceiver module.

•

Place the removed memory module, CF card, or HIM/MIM on an antistatic workbench, with the
face upward, or put it into an antistatic bag.