SMA SB 3000TL User Manual

Page 49

Advertising
background image

SB 4000TL-21

SB 5000TL-21

Initial input voltage

150 V

150 V

Maximum input current, input A

15 A

15 A

Maximum input current, input B

15 A

15 A

Maximum short-circuit current per input*

20 A

20 A

Maximum reverse current from the inverter in the
system for max. 1 ms

0 A

0 A

Number of independent MPP inputs

2

2

Strings per MPP input

2

2

Overvoltage category in accordance with
IEC 60664-1

II

II

* In accordance with IEC 62109-2: I

SC PV

AC Output

SB 4000TL-21

SB 5000TL-21

Rated power at 230 V, 50 Hz

4,000 W

4,600 W

Maximum apparent AC power

4,000 VA

5,000 VA

Rated grid voltage

230 V

230 V

Nominal AC voltage

220 V / 230 V /

240 V

220 V / 230 V /

240 V

AC voltage range*

180 V to 280 V

180 V to 280 V

Nominal AC current at 220 V

18.2 A

20.9 A

Nominal AC current at 230 V

17.4 A

20.0 A

Nominal AC current at 240 V

16.7 A

19.2 A

Maximum output current

22 A

22 A

Total harmonic distortion of the output current
with total harmonic distortion of the AC voltage
< 2%, and AC power > 50% of the rated power

≤4%

≤4%

Inrush current

< 20% of the nominal

AC current for a

maximum of 10 ms

< 20% of the nominal

AC current for a

maximum of 10 ms

Maximum output current under fault conditions

34 A

34 A

Rated power frequency

50 Hz

50 Hz

AC power frequency*

50 Hz / 60 Hz

50 Hz / 60 Hz

Operating range at AC power frequency 50 Hz

45 Hz to 55 Hz

45 Hz to 55 Hz

11 Technical Data