12 troubleshooting, 1 activating overload protection, Troubleshooting – SMA SI-TB-BOX-10 User Manual
Page 58: Activating overload protection

12 Troubleshooting
SMA America, LLC
58
SI_TDBOX-IA-eng-IUS122211
Installation Manual
12 Troubleshooting
12.1 Activating Overload Protection
The overload protection of the Smartformer was tripped. Activate the overload protection using the
following procedure.
1. Switch the overload protection to 0.
2. Switch the overload protection to 1.
☑ The overload protection stays set to 1 and the connected loads are supplied with voltage.
✖ What if the overload protection jumps back to a position between 0 and 1?
Possible cause of fault: The temperature in the autotransformer is still too high.
• Wait at least 10 minutes.
• Switch the overload protection to 0.
• Switch the overload protection to 1.
Possible cause of fault: Too many loads are connected via "Load L2".
• Switch off individual loads.
• Connect more loads via "Load L1".