Procedure:
1. In the drop-down list User group, select the user group for which the PUK was generated by
the SMA Service Line.
2. Enter the PUK in the field System password.
3. Select [Next>].
☑ Sunny Explorer displays the inverter in the system tree without a padlock icon.
4. Change the inverter password:
– Select the inverter in the system tree.
– Select the tab Settings.
– Select the parameter group User Rights > Access Control.
– Select [Edit].
– Assign password for relevant user group.
5. To unlock further inverters with a PUK, select Options > Change user group.
6. Assign a new system password (see Section "Changing the System Password", page 45).
8.5 SMA Grid Guard
SMA Grid Guard is a security concept for country-specific settings in the inverter which determine the
grid behavior within a utility grid. These settings (SMA Grid Guard parameters) are dependent on the
country standard configured in the inverter and can only be configured with the SMA Grid Guard
code.
In order to change SMA Grid Guard parameters, you will not only need to be logged in as Installer,
but you will also need your personal SMA Grid Guard code which can be obtained from
SMA Solar Technology AG. You can find the relevant application from the download area at
www.SMA-Solar.com.
Entering the SMA Grid Guard Code
Requirement:
☐ You must be logged into Sunny Explorer in the user group Installer.
%"/(&3
Lethal electric shock as a result of changing the internal safety specifications of the
inverter
Unauthorized changes to the SMA Grid Guard parameters void the operating license.
• Do not change any SMA Grid Guard parameters unless you have the express permission of
the grid operator.