SMA SB 1300TL User Manual

Page 33

Advertising
background image

5. Check whether the DC connectors have the correct polarity.

If the DC connector is equipped with a DC cable of the wrong polarity, the DC connector must
be assembled again. The DC cable must always have the same polarity as the DC connector.

6. Ensure that the open-circuit voltage of the PV array does not exceed the maximum input

voltage.

7. Connect the assembled DC connectors to the

inverter.

☑ The DC connectors snap into place.

6 Electrical Connection

SMA Solar Technology AG

Operating Manual

33

SB13-21TL-BE-en-11