5 Installation Procedure

16

YASKAWA ELECTRIC TOBP C730600 37B 1000-Series Option PG-X3 Installation Manual

4.

Prepare wire ends as shown in

Figure 6

.

Refer to Wire Gauges and Tightening

Torques on page 20

to confirm that the proper tightening torque is applied to each

terminal. Take particular precaution to ensure that each wire is properly connected

and wire insulation is not accidentally pinched into electrical terminals.

WARNING! Fire Hazard. Tighten terminal screws to the specified tightening torque. Loose electrical

connections could result in death or serious injury by fire due to overheating. Tightening screws beyond the

specified tightening torque may cause erroneous operation, damage the terminal block, or cause a fire.

NOTICE: Heat shrink tubing or electrical tape may be required to ensure that cable shielding does not

contact other wiring. Insufficient insulation may cause a short circuit that can damage the option or drive.

Figure 6

Figure 6 Preparing Ends of Shielded Cable

5.

Wire the motor PG encoder to the terminal block on the option. Refer to

Figure 8

for

wiring instructions.

Refer to Option Terminal Functions on page 21

for a detailed description of the

option board terminal functions.

Parameter Settings and Connections for Different Encoder Types

• Connecting a Single-Channel Encoder

When using a single-channel encoder in V/f with PG control mode, connect the

pulse output from the PG to the option and set drive parameter F1-21 to 0.

• Connecting a Two-Channel Encoder

When using a two-channel encoder, connect the A and B pulse outputs on the PG

to the option and set F1-21 to 1.

When using a two-channel encoder in Closed Loop Vector control mode, connect

pulse outputs A and B from the encoder to the corresponding terminals on the

option.

• Connecting a Two-Channel Encoder with Z Marker Pulse

When using a two-channel encoder with Z marker pulse, connect the A channel,

B channel, and Z pulse outputs to the corresponding terminals on the option.

Control Method

V/f with PG

Closed Loop Vector

No. of Encoders

1 CN5-C

2 CN5-B

1 CN5-C

2 CN5-B

Single Channel (A)

F1-21 = 0

F1-37 = 0

N/A

N/A

Two Channel (AB Quadrature)

F1-21 = 1

F1-37 = 1

No setting required No setting required

Two Channel with Marker (ABZ)

F1-21 = 1

F1-37 = 1

No setting required No setting required

Insulation

Shield sheath

Shield

PG option terminal

PG at motor

FE/SD

Ground Terminal

(Insulate with electrical tape

or shrink tubing)

X3