YASKAWA ELECTRIC TOBP C730600 37B 1000-Series Option PG-X3 Installation Manual

6 Related Parameters

6

Related Parameters

The following parameters are used to set up the drive for operation with the option. Set

parameters as needed. Parameter setting methods can be found in the drive Quick Start

Guide or Technical Manual.

Table 6 Related Parameters

No.

(Addr. Hex)

Name

Description

Control

Method

Values

A1-02

(102)

Control
Method
Selection

0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
5: Open Loop Vector Control for PM
6: Advanced Open Loop Vector Control for PM
7: Closed Loop Vector Control for PM

All Modes

Default:

<1>

Range:

<1>

F1-01

(380)

<2> <3>

PG 1 Pulses
per Revolution

Sets the pulses to be read from the pulse generator.

V/f w/ PG
CLV
CLV/PM

Default:

<1>

Min:

<1>

Max:

<1>

F1-02

(381)

PG Feedback
Loss Operation
Selection

Sets the stopping method when the PG becomes
disconnected (PGo).
0: Ramp to stop (decelerates at time set to C1-02)
1: Coast to stop
2: Fast Stop (decelerates at the time set to C1-09)
3: Continue running
4: No alarm display
Note: Due to potential damage to the motor and
machinery, only use the “Continue running” and “No
alarm display” settings under special circumstances.

V/f w/ PG
CLV
CLV/PM

Default: 1
Range:

<1>

F1-03

(382)

PG Overspeed
Operation
Selection

Sets the stopping method when overspeed is
detected.
0: Ramp to stop (decelerates at time set to C1-02)
1: Coast to stop
2: Fast Stop (decelerates at the time set to C1-09)
3: Continue running
Note: Due to potential damage to the motor and
machinery, only use the “Continue running” setting
under special circumstances.

V/f w/ PG
CLV
CLV/PM

Default: 1
Range: 0 to 3

F1-04

(383)

PG Deviation
Operation
Selection

0: Ramp to stop (decelerates at time set to C1-02)
1: Coast to stop
2: Fast Stop (decelerates at the time set to C1-09)
3: Continue running
Note: Due to potential damage to the motor and
machinery, only use the “Continue running” setting
under special circumstances.

V/f w/ PG
CLV
CLV/PM
AOLV/PM

Default:

<1>

Range: 0 to 3