5 Installation Procedure

YASKAWA ELECTRIC TOBP C730600 37B 1000-Series Option PG-X3 Installation Manual

19

8.

Set drive parameters for proper motor rotation.
With a two-channel or three-channel encoder, the leading pulse determines the

motor rotation direction. A PG signal with leading A pulse is considered to be

rotating forward (counter-clockwise when viewing rotation from motor load side).

Figure 9

Figure 9 Displacement of A and B Pulses

After connecting the PG outputs to the option, apply power to the drive and

manually rotate the motor and check the rotation direction by viewing monitor U1-05

on the digital operator.

Reverse motor rotation is indicated by a negative value for U1-05; forward motor

rotation is indicated by a positive value.

If monitor U1-05 indicates that the forward direction is opposite of what is intended,

reverse the two A channel wires with the two B channel wires on option terminal

TB1 as shown in

Figure 10

.

Figure 10

Figure 10 A Channel and B Channel Wire Switching

If switching the wires is inconvenient, set drive parameter F1-05/F1-32 to 1 to switch

the direction of how the option reads pulses from the PG output.

Please note that when the drive is initialized using A1-03 =1110, 2220, 3330, the

value for F1-05/F1-32 will reset to factory default and the parameter will need to be
adjusted again to switch the direction.

A pulse

B pulse

The A pulse leads, followed

by the B pulse displaced at 90 degrees

Time →

X3

A+

B+

A

B

Z+

SD FE

Z

A+

B+

A

B

Z+

SD FE

Z

X3