Installation

Observe the following precautions when installing SERVOPACK.

• Install SERVOPACK perpendicular to the wall so that the front panel (digital operator

mounted face) faces outward.

• Firmly secure the SERVOPACK through two or four mounting holes depending on the

SERVOPACK capacity.

• Install SERVOPACK so that SERVOPACK can be cooled by natural convection or fan.

„

Installation Sites

For installation sites, use proper care with the following notes.

Situation

Notes on Installation

When installed in a control panel

• Design the control panel size, unit layout, and cooling

method so that the temperature around the periphery of the
SERVOPACK does not exceed 55

°C.

• When installing multiple SERVOPACKs side by side in a

control panel, install cooling fans sand provide sufficient
space around each SERVOPACK to allow cooling by fan
and natural convenction.

When installed near a heating unit

Suppress radiation heat from the heating unit and a tempera-
ture rise caused by convection so that the temperature around
the periphery of the SERVOPACK does not exceed 55

°

C.

When installed near a source of
vibration

Install a vibration isolator underneath the SERVOPACK to
prevent it from receiving vibration.

When installed in a place receiving
corrosive gases

Corrosive gases do not immediately affect the SERVOPACK
but will eventually cause contactor-related devices to malfunc-
tion. Take appropriate action to protect against corrosive gases.

Others

• Avoid installation in a hot and humid place or where exces-

sive dust or iron powder is present in the air.

• Be sure there is no condensation or freezing.
• Keep the surrounding air temperature 45

°C or less to ensure

long-term reliability.

Cooling fan

50 mm (1.97in) min.

10 mm (0.39in) min.

30 mm (1.18in) min.

Cooling fan

50 mm (1.97in) min.