12 general specifications – Yaskawa Σ-II Series User Manual

Page 25

Advertising
background image

12 General Specifications

E-23

12 General Specifications

The following table shows the SERVOPACK general specifications.

Item

Specifications

Surrounding Air/Storage Tem-
perature

0 to +55

°C/-20 to +85 °C

Operating/Storage Humidity

90%RH or less (non-condensing)

Operating Environment

• Installation category (Overvoltage category): III
• Pollution degree: 2
• Protection class: 10
• Altitude: 1,000 m max.

Vibration Resistance

4.9 m/s

2

Shock Resistance

19.6 m/s

2

Voltage Resistance

• Voltage: 1,500 V rms AC, for one minute
• Braking current: 30 mA
• Frequency: 50 Hz or 60 Hz
• Voltage applied points

100 V and 200 V SERVOPACK: Between the frame ground
and the power where the terminals L1, L2, L3, L1C, L2C, U,
V, and W connect.
400 V SERVOPACK: Between the frame ground and the
power where the terminals L1, L2, L3, U, V, and W connect.

Insulation Resistance

10 M

Ω

min. (500 VDC megger) between the frame ground

and the power terminals U, V, and W

Overseas Standards
(Pending Approval)

• UL Standards: UL508C
• EMC Directives: EN61000-6-2, EN55011 (group 1 class A)
• Low Voltage Directive: EN50178