Caution – Yaskawa DS391 User Manual

Page 3

Advertising
background image

DWG. NO. 02Y00025-0297

SHEET NO. 3 OF 7

REL. 01/30/91

( m - d f )

Refer to Sheet 1 for latest change.

Table 1. Specifications

Parameter

Analog Monitor (AO-08)

Analog Monitor (AO-12)

Output Resolution

8 Bits (1/256)

11 Bits + sign (1/2048)

Output Voltage

0 to +10V (non-isolated)

–10V to +10V (non-isolated)

Output Channels

2

2

Control voltage input (from GPD 515, GPD 503 or VCD 703): 24V (isolated)

Table 2. Terminal Functions of AO-08 and AO-12

Signal Level

Terminal

Function

GPD 515

GPD 503

VCD 703

Notes

A0-08

A0-12

A0-08 A0-12

A0-08

A0-12

TD1

Analog signal
output channel 1

0 - 10V

0 - 10 V — Output impedance: 200

0 - 10V

or

0 - 10V 0 - 10 V 0 - 10V

or

TD2

Analog signal

±10V

±10V

— Terminal screws are metric

output channel 2

(1)

(2)

size M3.

TD3

Output Common

0V

(1)

Selectable by setting of drive parameter H4-07.

(2)

Selectable by setting of drive constant Sn-28 digit X X X X .

5. Connect the Analog Monitor's grounding (green) wire to terminal 12 of the drive.

6. Wiring. See Figure 3 for Analog Monitor connections. See Table 2 for terminal functions.

CAUTION

ANALOG MONITOR (I.E. CONTROL CIRCUIT) WIRING MUST
REMAINSEPARATE FROM MAIN CIRCUIT INPUT/OUTPUT
WIRING.

CAUTION

TO PREVENT ERRONEOUS OPERATION CAUSED BY NOISE
INTERFERENCE, USE SHEILDED CABLE FOR CONTROL
SIGNAL WIRING, AND LIMIT DISTANCE TO 50M (165 FEET) OR
LESS.

Advertising