Ao-08 or ao-12 board, Motor mccb – Yaskawa DS391 User Manual
Page 4

DWG. NO. 02Y00025-0297
SHEET NO. 4 OF 7
REL. 01/30/91
( m - d f )
Refer to Sheet 1 for latest change.
Figure 3. Interconnection for Analog Monitor (AO-08 or AO-12) Circuit
12
GPD 515,
GPD 503,
or
VCD
703
L1
L2
L3
T1
T2
T3
E
TD1
AO-08 or AO-12 BOARD
33000 PF
0V
0V
TYPICAL CIRCUIT
BOTH CHANNELS
0V
D/A
CONVERTER
200
I M
MOTOR
MCCB
SHIELD
3CN
3CN
(GREEN)
FM
AM
+
+
-
-
10K
10K
MTR
CAL
MTR
CAL
TD3
TD2
Table 3. Programming For Output Signal Scaling
Gain
(2)
Drive
Terminal
Parameter/
Setting Range
Increment
Factory Setting
Remarks
Constant
GPD
TD1
F4-02
0.00 to 2.50
0.01
1.00
10V / 1.00
(1)
515
TD2
F4-04
0.00 to 2.50
0.01
0.50
10V / 1.00
(1)
GPD
TD1
bn-11
0.01 to 2.55
0.01
1.00
10V / 1.00
(1)
503
TD2
bn-12
0.01 to 2.55
0.01
0.50
10V / 1.00
(1)
VCD
TD1
bn-23
0.0 to 10.000
0.001
1.000
10V / 1.000
(1)
703
TD2
bn-25
0.0 to 10.000
0.001
1.000
10V / 1.000
(1)
(1)
Output signal level can be up to +11V by setting program parameters/constants.
(2)
A gain of 0.5 will set 5V = 100%; a gain of 2.0 will set 10V = 50%.