4.2 Monitors (U1-XX)

Monitor Number

Modbus Address

Monitor Name

Digital Operator

Display

Description

Scaling for Multi-

function Analog

Outputs Terminals

FM and AM

(H4-01, H4-04)

Unit

Access Level For All

Control Modes *1

U1-90 720H

PID Feedback

PID Feedback

Displays the PID
feedback as a
percentage of the
maximum output
frequency.

100%: Maximum

Output Frequency

(E1-04)

0.1

%*2

A

U1-91 721H

PID Input

PID Input

Displays the PID input
value as a percentage
of the maximum output
frequency.

100%: Maximum

Output Frequency

(E1-04)

0.1

%*2

A

U1-92 722H

PID Output

PID Output

Displays the PID
output value as a
percentage of the
maximum output
frequency.

100%: Maximum

Output Frequency

(E1-04)

0.1

%*2

A

U1-93 723H

PID Proportional Output

PID P Output

Displays the PID
proportional value as a
percentage of the
maximum frequency.

100%: Maximum

Output Frequency

(E1-04)

0.1

%*2

A

U1-94 724H

PID Integral Output

PID I Output

Displays the PID
integral value as a
percentage of
maximum output
frequency.

100%: Maximum

Output Frequency

(E1-04)

0.1

%*2

A

U1-95 725H

PID Derivative Output

PID D Output

Displays the PID
derivative value as a
percentage of the
maximum output
frequency.

100%: Maximum

Output Frequency

(E1-04)

0.1

%*2

A

U1-96 726H

PID Setpoint

PID Setpoint

Displays the PID
setpoint as a
percentage of the
maximum output
frequency.

100%: Maximum

Output Frequency

(E1-04)

0.1

%*2

A

U1-97 727H

Encoder Input

Encoder Input

Displays the frequency
of the raw encoder
input of the digital
velocity follower
function.

N/A

0.1

kHz

A

U1-98 728H

Encoder Reference

Encoder Ref.

Displays the frequency
reference generated by
the encoder input of
the digital velocity
follower function.

100%: Maximum

Output Frequency

(E1-04)

0.1

Hz

A

*1: Access Level (A1-01): Q = “Quick Start”, A = “Advanced”, F = “Factory”.