4.3 Multi-function Digital Input Settings (H1-0X)

Setting

Display

Description

Available For All

Control Modes

80

Positive Integral

Hold

Closed: Integral is permitted to decrease, but not increase.

81

Negative

Integral Hold

Closed: Integral is permitted to increase, but not decrease.

√: Available.

4.4 Multi-function Digital Output Settings (H2-0X)

Setting

Display

Description

Available For All

Control Modes

40 Feedback

High

Closed: PID feedback has exceeded P1-02 level for the time
set in P1-03.

41 Feedback

Low

Closed: PID feedback has fallen below the P1-05 level for the
time set in P1-06.

√: Available.

4.5 Faults

Fault Display

Description

Cause

Countermeasures

FRH

Feedback Range

High

PID feedback out of range
(high). Motor will coast to a
stop.

P1-01 = 4 or 5 and the PID
feedback has exceeded the
P1-02 level for the time set
in P1-03.

Correct the cause of the

high feedback signal.

FRL

Feedback Range

Low

PID feedback out of range
(low). Motor will coast to a
stop.

P1-01 = 4 or 5 and the PID
feedback has fallen below
the P1-05 level for the time
set in P1-06.

Correct the cause of the

low feedback signal.

OPE12

PID / DVF Err

1. PID limit setting error


2. Motor 2 control method
is Flux Vector or V/Hz
w/PG and the frequency
reference source is PG
Option Card

3. PG-X2 or PG-B2 card
installed, control method is
Flux Vector or V/Hz w/PG,
and the frequency
reference source is PG
option card

1. P2-01 is set greater than
B5-06

2. B1-01 = 5,
E3-01 = 1 or 3,
and H1-XX = 16



3. PG-X2 / PG-B2 installed,
A1-02 = 1 or 3,
and B1-01 = 5


Correct the parameter

settings.


4.6 Alarms

Alarm Display

Description

Cause

Countermeasures

FRH

Feedback Range

High

PID feedback out of range

(high)

P1-01 = 2 or 3 and the PID
feedback has exceeded the
P1-02 level for the time set
in P1-03.

Correct the cause of the

high feedback signal.

FRL

Feedback Range

Low

PID feedback out of range

(low)

P1-01 = 2 or 3 and the PID
feedback has fallen below
the P1-05 level for the time
set in P1-06.

Correct the cause of the

low feedback signal.