Yaskawa F7 Drive Enhanced PID With Digital Velocity Follower User Manual

Page 8

Advertising
background image

Date: 08/08/05, Rev: 05-08

Page 8 of 17

TM.F7SW.058

4.1 Parameters (continued)

Parameter

Number

Modbus Address

Parameter Name

Digital Operator

Display

Description

Range

Default

Change During

Run

Access Level For All

Control Modes *1

P2-02 60BH

PID Output Gain 2

Output Gain 2

This parameter sets the gain at the
output of the PID. Functions the same as
PID Output Gain (B5-10), but with finer
resolution (0.01 versus 0.1). The total
output gain is determined by B5-10 x P2-
02.

0.00

~

25.00

1.00 No A

P2-03 60CH

PID Setpoint Offset

Setpoint Offset

This parameter sums with the PID
setpoint (analog input, pulse input,
network communication, or parameter) to
provide an offset.

-100.0

~

+100.0

%

0.0 No A

P2-04 60DH

PID Trim Mode

Selection

PID Trm Mode Sel

This parameter selects how the PID
output will trim the frequency reference.
Active only when b5-01 = 3 or 4.

0: Constant

The PID output trim is independent of
the frequency reference.

1: Freq Ref Prop

The PID output trim is proportional to
the frequency reference.

0 ~ 1

0

No

A

P2-05 60EH

Frequency

Reference

Proportional Trim

Lower Limit

FrefProp Low Lim

This parameter sets the lower limit of the
PID output trim of the frequency
reference when P2-01 = 1 (trim is
proportional to the frequency reference).
Active only when b5-01 = 3 or 4 and P2-
04 = 1.

0.00

~

100.00

%

10.00 Yes

A

P3-01 614H

Master Encoder

Pulses per
Revolution

Master PG PPR

This parameter sets the resolution, in
pulses per revolution, of the encoder
used in the digital velocity follower
function. This applies to the PG-W2, PG-
X2, and PG-B2 cards. Parameter E2-04
(Motor Poles) must also be correctly set.

The PG-W2 and PG-X2 have a
maximum input frequency of 300 kHz.
The PG-B2 has maximum input
frequency of 32 kHz.

1
~

60,000

1024 No A

P3-02 615H

Ratio Numerator

Ratio Numerator

This parameter sets the numerator of the
gear ratio in the digital velocity follower
function.

1
~

65,535

10000 Yes

A

P3-03 616H

Ratio Denominator

Ratio Denominator

This parameter sets the denominator of
the gear ratio in the digital velocity
follower function.

1
~

65,535

10000 Yes

A

*1: Access Level (A1-01): Q = “Quick Start”, A = “Advanced”, F = “Factory”.