Yaskawa F7 Drive Enhanced PID for Air Compressor User Manual

Page 7

Advertising
background image

Date: 08/01/05, Rev: 05-08

Page 7 of 17

TM.F7SW.096

4.1 Parameters (continued)

Parameter

Number

Modbus Address

Parameter Name

Digital Operator

Display

Description

Range

Default

Change During

Run

Access Level For All

Control Modes *1

P2-02 60BH

PID Output Gain 2

Output Gain 2

This parameter sets the gain at the
output of the PID. Functions the same
as PID Output Gain (B5-10), but with
finer resolution (0.01 versus 0.1). The
total output gain is determined by B5-
10 x P2-02.

0.00

~

25.00

1.00 No A

P2-03 60CH

PID Setpoint Offset

Setpoint Offset

This parameter sums with the PID
setpoint (analog input, pulse input,
network communication, or parameter)
to provide an offset.

-100.0

~

+100.0

%

0.0 No A

P2-04 60DH

PID Trim Mode

Selection

PID Trm Mode Sel

This parameter selects how the PID
output will trim the frequency reference.
Active only when b5-01 = 3 or 4.

0: Constant

The PID output trim is independent
of the frequency reference.

1: Freq Ref Prop

The PID output trim is proportional
to the frequency reference.

0 ~ 1

0

No

A

P2-05 60EH

Frequency

Reference

Proportional Trim

Lower Limit

FrefProp Low Lim

This parameter sets the lower limit of
the PID output trim of the frequency
reference when P2-01 = 1 (trim is
proportional to the frequency
reference). Active only when b5-01 = 3
or 4 and P2-04 = 1.

0.00

~

100.00

%

10.00 Yes

A

P2-06

60FH

Wake-Up Delay

Timer

Wake Up Delay

This parameter determines the time
delay after the frequency reference
exceeds the sleep level, that the drive
will resume running.

0.0

~

600.0

sec

1.0 No A

P2-07

610H

Minimum Off-Time

during sleep

operation

Min Off Time

This parameter determines the
minimum amount of time the drive will
be off during sleep mode to allow the
pressure in the sump to dissipate.

0.0

~

6000.0

sec

30.0 No A

P2-08

611H

Blowdown Valve

Delay Time

Blowdown Delay

This parameter determines (after the
drive is started or re-started after a
sleep cycle) how long the drive has to
run for before closing the multi-function
digital output “blowdown valve”.

0.0

~

120.0

sec

3.0 No A

*1: Access Level (A1-01): Q = “Quick Start”, A = “Advanced”, F = “Factory”.