4.1 Parameters (continued)

Parameter

Number

Modbus Address

Parameter Name

Digital Operator

Display

Description

Range

Default

Change During

Run

Access Level For All

Control Modes *1

P2-09 612H

Custom Units

Display Selection

Custom Units

This parameter determines what
custom units are displayed for U1-01,
D1-XX, and U1-90 thru U1-96.

0: No units displayed
1: PSI
2: kPa
3:

o

F


Note: Only applicable when O1-03 ≥ 40
(custom units).

0 ~ 3

1

No

A

P2-10 612H

Output Monitor

Units

Output Mon Units

Selects the units & scaling for the
following keypad monitors: U1-02, U1-
05, U1-20, and U1-46. Works in the
same fashion as parameter O1-03.

0: Hz
1: %
2 ~ 38: RPM (Set motor poles)
40 ~ 39999: Custom

0 ~

39999

0 No A

*1: Access Level (A1-01): Q = “Quick Start”, A = “Advanced”, F = “Factory”.