Yaskawa F7 Drive Enhanced PID for Air Compressor User Manual

Page 9

Advertising
background image

Date: 08/01/05, Rev: 05-08

Page 9 of 17

TM.F7SW.096

4.2 Monitors (U1-XX)

Control Mode *1

Monitor Number

Modbus Address

Monitor Name

Digital

Operator

Display

Description

Scaling for Multi-

function Analog

Outputs

Terminals

FM and AM

(H4-01, H4-04)

Unit

V/f

V/f w/ PG

Open Loop

Vector

F

lux Vector

U1-01 040H

Frequency

Reference

Frequency

Ref

Displays the
frequency
reference.

100%:

Maximum Output

Frequency

(E1-04)

0.01

Hz

*2

Q Q Q Q

U1-02 041H

Output

Frequency

Output Freq

Displays the output
frequency.

100%:

Maximum Output

Frequency

(E1-04)

0.01

Hz

*3

Q Q Q Q

U1-05 044H

Motor Speed

Motor Speed

Displays the
encoder feedback
speed or estimated
motor speed.

100%:

Maximum Output

Frequency

(E1-04)

0.01

Hz

*3

- Q Q Q

U1-20 053H

Soft Starter

Output

SFS Output

Displays the
frequency
reference after the
Accel, Decel, and
S-curve ramps.

100%:

Maximum Output

Frequency

(E1-04)

0.01

Hz

*3

Q Q Q Q

U1-46 06DH

Feed-Forward

Speed

FF Estimate

SPD

Displays the
estimated feed-
forward speed
(Flux Vector only).

100%:

Maximum Output

Frequency

(E1-04)

0.01

Hz

*3

- - - F

U1-90 720H

PID Feedback

PID Feedback

Displays the PID
feedback as a
percentage of the
maximum output
frequency.

100%:

Maximum Output

Frequency

(E1-04)

0.1%

*2

Q Q Q Q

U1-91 721H

PID Input

PID Input

Displays the PID
input value as a
percentage of the
maximum output
frequency.

100%:

Maximum Output

Frequency

(E1-04)

0.1%

*2

Q Q Q Q

U1-92 722H

PID Output

PID Output

Displays the PID
output value as a
percentage of the
maximum output
frequency.

100%:

Maximum Output

Frequency

(E1-04)

0.1%

*2

Q Q Q Q

U1-93 723H

PID

Proportional

Output

PID P Output

Displays the PID
proportional value
as a percentage of
the maximum
frequency.

100%:

Maximum Output

Frequency

(E1-04)

0.1%

*2

Q Q Q Q

*1: Access Level (A1-01): Q = “Quick Start”, A = “Advanced”, F = “Factory”.
*2: Unit and scaling based on O1-03 (Display Scaling) setting. When O1-03 ≥ 40 (custom units), the displayed

units on the keypad are determined by parameter P2-09.

*3: Unit and scaling based on P2-10 (Output Monitor Units) setting. Parameter P2-10 operates exactly the same

way as O1-03. When P2-10 ≥ 40 (custom units), the displayed units on the keypad are determined by
parameter P2-09.

Advertising