Yaskawa F7 Drive Output Voltage PID User Manual

Page 3

Advertising
background image

Date: 05/05/05, Rev: 05-05

Page 3 of 8

TM.F7SW.061

2.0 Changes from Standard Product

a. The energy savings function (B8-01 = 1) cannot be used in conjunction with the output voltage PID

controller in the V/Hz control method (A1-02 = 0) or an “OPE12 - Energy Save ON” fault will occur.

b. Parameters N9-10, N9-14, and N9-15 have been moved from the “Factory” access level to the “Advanced”

access level (A1-01) in the V/Hz control mode (A1-02 = 0) for easier access. The factory should be
consulted before adjusting these parameters.


3.0 Limitations

a. The output voltage PID controller is available only in the V/Hz control mode (A1-02 = 0).
b. The “P” group parameters cannot be used in the “User Access Level” (A1-03 = 1110).
c. This software is specifically designed for the applications described in section 1. This software should

not be used to control a motor.


4.0 Related Parameters and Functions

4.1 Parameters

Control Mode

*1

Paramete

r

Numb

er

Modbu

s

Addre

ss

Parameter Name

Digital Operator

Display

Description

Ran

ge

Default

Cha

nge

Duri

ng Run

V/f

V/f w/ P

G

Open Lo

op

Vector

Flu
x

Vector

N9-10 5D9h

Automatic

Voltage Regulator

Time

AVR Time

Sets the time constant of
the Automatic Voltage
Regulator (AVR). The
AVR regulates the drive’s
output voltage by
compensating for
changes in the DC bus
voltage (input drive
voltage).

0.0 ~

100.0

msec

1.0 No

A

*2

F F F

N9-14 5DDh

Power Factor
Angle Filter 1

Pwr Angle Flt 1

Sets the filter time of
power factor angle
detection function used
during acceleration.

0 ~

1000

msec

5 No

A

*2

F - -

N9-15 5DEh

Power Factor
Angle Filter 2

Pwr Angle Flt 2

Sets the filter time of
power factor angle
detection function used
during constant frequency
output (speed agree).

0 ~

1000

msec

5 No

A

*2

F - -

P1-01 600h

Output Voltage

Setpoint

Output V Setpt

Sets the target value of
the Output Voltage PID
controller. The drive’s
output voltage will be
modulated to keep the
analog input “output
voltage feedback” signal
equal to this setpoint.

Note: A setting of 0.0VAC
disables the Output
Voltage PID controller.

0.0 ~

600.0

VAC

460.0 Yes A - - -

*1: Access Level (A1-01): Q = “Quick Start”, A = “Advanced”, F = “Factory”.
*2: Moved from the “Factory” access level to the “Advanced” access level. Consult the factory before adjusting.