7.0 Typical Parameter Settings

7.1 Parameter Settings for a Typical Power Supply Application (480V Drive).

Parameter

Description

Setting

A1-02

Control Method

0 (V/F Control)

B1-01

Reference Source

0 (Keypad)

B1-03

Stopping Method

1 (Coast to Stop)

B1-04

Reverse Operation

1 (Disabled)

C1-01 Acceleration

Time

1

0.20sec

C1-02 Deceleration

Time

1

0.20sec

C2-01

S-curve Time 1

0.00sec

C2-02

S-curve Time 2

0.00sec

C2-03

S-curve Time 3

0.00sec

C4-01

Torque Compensation Gain

0.00

C6-01

Operation Duty Selection

1 (Normal Duty 1) *3

C6-02

Carrier Frequency Selection

3 (8.0kHz) *3

D1-01

Frequency Reference 1

60.00Hz

E1-03

V/F Pattern Selection

FF (Custom w/o Limit)

E1-05

Maximum Output Voltage

460VAC

H3-05

Terminal A3 Function Selection

20 (Output Voltage Feedback)

L2-01

Powerloss Detection Selection

2 (CPU Ride Through)

L2-03

Minimum Base Block Time

0.1sec

L2-04

Voltage Recovery Ramp Time

0.0sec

L2-05

Undervoltage Detection Level

150VDC *3

L3-01

Stall Prevention During Acceleration

0 (Disabled)

L3-04

Stall Prevention During Deceleration

0 (Disabled)

L3-05

Stall Prevention During Running

0 (Disabled)

L8-05

Input Phase Loss Selection

0 (Disabled)

L8-07

Output Phase Loss Selection

0 (Disabled)

N1-01

Hunting Prevention Selection

0 (Disabled)

N9-10

AVR Time Constant

100.0msec *4

N9-14

Power Factor Detection Time 1

1000.0msec *4

N9-15

Power Factor Detection Time 2

1000.0msec *4

P1-01

Output Voltage PID Setpoint

460VAC

P1-02

Output Voltage PID Gain

3.00

P1-03

Output Voltage PID Integral Time

0.30sec

P1-07

Output Voltage Feedback Scaling (Sensor

Dependent)

VAC

*3: Changing these settings to the values shown may require either a higher capacity drive or additional

hardware. Please consult the Industrial Applications department at Yaskawa before adjusting.

*4: Formerly factory access level parameters. Please consult the Industrial Applications department at Yaskawa

before adjusting.