Yaskawa America, Inc.

Operation panel STOP

key function

n007

0

o2-02

1

V74X

V1000-4X

n007 0

o2-02 1

n007 1

o2-02 0

Frequency reference in

local mode

n008

0

-

-

As the V1000-4X has no operator panel

pot, no selection available.

Frequency reference

from operator ENTER

key selection

n009

0

o2-05

0

n009 0

o2-05 0

n009 1

o2-05 1

Operator panel

disconnect fault

detection selection

n010

0

o2-06

o2-09

dep.

n010 0

o2-06 = 0

n010 1

o2-06 = 1

Max. output frequency

(FMAX)

n011

50.0 Hz

E1-04

E1-03,

o2-09

dep./

E5-01

dep. If

A1-02=5

Max. output voltage

(VMAX)

n012

200.0 V
400.0 V

E1-05

E5-01

dep. If

A1-02=5

The V1000-4X has two different settings

for VBASE and VMAX. The initial

setting for VBASE is 0.0V which means,

that VMAX is output at FBASE (like in

V74X).

Output voltage at base

frequency (VBASE)

n012

200.0 V
400.0 V

E1-13

0.0VAC

Base frequency

(FBASE)

n013

50.0 Hz

E1-06

E1-03,

o2-09

dep./

E5-01

dep. If

A1-02=5

Mid. output frequency

(FMID)

n014

1.35 Hz

E1-07

A1-02,

E1-03,

o2-09

dep.

Mid. output voltage

(VMID)

n015

12.0 V

E1-08

Min. output frequency

(FMIN)

n016

1.3 Hz

E1-09

A1-02,

E1-03,

o2-09

dep./

E5-01

dep. If

A1-02=5

Min. output voltage

(VMIN)

n017

12.0 V

E1-10

A1-02,

E1-03,

o2-09

dep.

Acceleration /

deceleration time

resolution selection

n018

0

C1-10

1

n018 0

C1-10 1

n018 1

C1-10 0

Acceleration time 1

n019

10.0

sec

C1-01

10.0

sec

Deceleration time 1

n020

10.0

sec

C1-02

10.0

sec

Acceleration time 2

n021

10.0

sec

C1-03

10.0

sec

Drive

Parameter

Function

V74X

V1000-4X

Note

Param.

No.

Initial

Value

Set

Value

Param.

No.

Initial

Value

Set

Value