3 ratings summary, Ratings summary – Yaskawa VS606 V74X V7 to V1000 User Manual

Page 6

Advertising
background image

Product Transition Guide

PL. V1000-4X.01 Rev: 6/22/10

PL.V1000-4X.01 Transition Guide 6/22/10
Page 6 of 32
Yaskawa America, Inc.

1.3 Ratings Summary

The following table summarizes the output current ratings for the V1000-

4X

and V7

4X

with respect to the specific drive

model. Please note that the V7

4X

current rating is based on a “Heavy Duty” rating, whereas, the V1000-

4X

factory default is

based on a “Normal Duty” rating. See below for an explanation of the differences between “Heavy” and “Normal” duty
ratings.

Note: If the V1000-4X drive is set to “Heavy Duty”, the current ratings are the same as the V74X drive.

Rated

Input Voltage

V74X Drive

Model Number

CIMR-V7CU

Heavy Duty

V1000-4X Drive

Model Number

CIMR-V

Normal Duty

Rated Output

Current (Amps)

Nominal HP

Rated Output

Current (Amps)

Nominal HP

200V,

3-Phase

20P14
20P24
20P44

0.8

1.6
3.0

1/8

1/4

1/2

2A0001GAA
2A0002GAA
2A0004GAA

1.2
1.9
3.5

1/8 & 1/4

1/4

1/2 & 3/4

20P74
21P54

5.0
8.0

3/4 & 1

2

2A0006GAA
2A0010GAA

6.0
9.6

1

2 & 3

22P24
23P74

11.0
17.5

3
5

2A0012GAA
2A0020GAA

12.0
19.6

3
5

25P54
27P54

25.0

33.0

7.5

10

2A0030GAA
2A0040GAA

30.0

40.0

7.5 & 10

10

400V,

3-Phase

40P24
40P44

1.2
1.8

1/2
3/4

4A0001GAA
4A0002GAA

1.2
2.1

1/2

3/4 & 1

40P74
41P54

3.4
4.8

1 & 2

3

4A0004GAA
4A0005GAA

4.1
5.4

2
3

42P24
43P74
45P54

5.5
8.6

14.8

3
5

7.5 & 10

4A0007GAA
4A0009GAA
4A0011GAA

6.9
8.8

11.1

4
5

7.5

45P54
47P54

14.8
18.8

7.5 & 10

10

4A0018GAA
4A0023GAA

18.0
24.0

10
15

Advertising