Yaskawa Varispeed-686SS5 CIMR-SSA User Manual

Page 46

Advertising
background image

4

OPERATION

47

Step

Description

Key Sequence

Digital Operator Display

13

Motor capacity selection setting

• Move to motor capacity selection (E1-02).

RESET

14

• Verify the set value of motor capacity

selection.

DATA

ENTER

(Example: 200V 1750 min

-1

7.5kW)

15

• Set correct value.

(Refer to Table A-6 for the set value of
motor capacity selection.)

RESET

(Example: 200V 1450 min

-1

7.5kW)

16

• Write-in the value.

DATA

ENTER

Displays for 0.5 seconds.

Setting completed.

17

• Return to constant No. display.

DSPL

18

Motor rated current setting

• Move to motor rated current (E1-04).

RESET

19

• Verify the set value.

DATA

ENTER

G

(Example: 200V 1450 min

-1

7.5kW)

20

• Set rated current according to value on

motor nameplate.

RESET

G

21

• Write-in the value.

DATA

ENTER

Displays for 0.5 seconds.

Setting completed.

G

22

• Return to constant No. display.

DSPL

23

• Repeat the same procedures for

18

to

21

as

for E1-09, 10, 11, 13.
(Add C2-12 setting in open loop vector
control.)
Furthermore, when using a special motor,
set motor base min

-1

(E1-07) and motor

maximum min

-1

(E1-06).

GGG

GGG

24

• Return to constant No. display.

DSPL

25

Return to drive mode.

DRIVE

PRGM

G

Advertising