5 Installation Procedure

18

YASKAWA ELECTRIC TOEP YEAOPT 03 - V1000 Option DI-100 120 Vac Interface Installation Manual

Figure 8

Figure 8 120 Vac External Control Wiring (customer wiring) to DI-100 Option

Figure 9 Wiring Diagram Example

DI-100 Option

120 Vac External
Control Wiring

120 VAC

INTERFACE

CARD

120 VAC

X2

S1

S2

S3

S4

S5

S6

S7

SC Common

S1 Forward run/stop

S2 Reverse run/stop

S3 External fault

S4 Fault reset

S5

Multi-step speed 1
mail/aux switch

S6 Multi-step speed 2

S7 Jog reference

FWD

REV

S3

S4

S5

S6

X2

X1

Yaskawa V1000
AC Drive

S7

Advertising