The iQpump Micro is operated in HAND mode by performing the following tasks:
·

Program all parameters

·

Verify motor rotation direction

19. HAND MODE

Press to access HAND Speed. Use to change HAND Speed value.

Press to save value.

Set parameter P5-01 ‘HAND Mode Ref.’ to ‘0’ to adjust the hand mode reference
from an external 0 – 10V signal connected to terminals TB1-1, A1 and AC.

Hand Speed Reference from Analog Input (0 to 10 Vdc)

PRESS TO TURN OFF

PRESS HAND MODE

Press to access HAND Speed. Use to change HAND Speed value.

Press to save value.

LED Digital Operator

LCD Digital Operator

Set parameter P5-01 ‘HAND Mode Ref.’ to ‘0’ to adjust the hand mode reference
from an external 0 – 10V signal connected to terminals TB1-1, A1 and AC.

Hand Speed Reference from Analog Input (0 to 10 Vdc)

0 to 10 Vdc Connection

P1

E(G)

0 ~ 10 Vdc

P2

PC

A1

A2

+V

AC

AM

AC

MP

Cable

Shield

P1

0 to 10 Vdc Connection

P1

E(G)

0 ~ 10 Vdc

P2

PC

A1

A2

+V

AC

AM

AC

MP

Cable

Shield

P1

Sleep and Anti-No-Flow (ANF) Detection

NOTE: Ensure the pump system is regulating pressure/flow satisfactory while operating under normal running conditions prior to
adjusting Anti-No-Flow operation.
Verify No-flow/Sleep operation
a. Continue to Step 1 below if pump operation is sstable.
b. Disable Anti-No-Flow function if pump operation is u

unstable.

-Set parameter P2-23 = 0.00% and adjust PI control parameters b5-02 and b5-03 to stabilize pump system.
-Refer to the iQpump Micro User Manual (Document No.TOEPYAIQPM03) for additional information.

c. Re-enable the Anti-No-Flow function by setting P2-23 to 0.40% and continue to Step 1 to verify no-flow/sleep operation once the
system is stable.

Step 1: Verify the system holds pressure by creating a no-flow situation (e.g. close off discharge valve).

Step 2: Press the OFF button on the digital operator, wait 1 minute until system stabilizes and verify system pressure feedback
using parameter U1-91. Adjust P2-25 to the actual delta pressure drop plus 1 PSI if the pressure drops more than 3 PSI (use
Monitor U1-91).

Example:

Setpoint is 80 PSI, pressure feedback U1-91 shows 76 PSI, P2-25 should be 4 + 1 or 5 PSI.

Note: This value should always be more than the P1-04 Start Level. If not, the system pressure is not holding and must be
corrected or the pump system will continue to cycle on and off.

Step 3: Operate the system in normal AUTO operation with flow. Observe monitor U1-99 “ANF Timer” and verify the value is
increments and resets to zero continuously. If the value holds at 10 sec. (P2-24) increase P2-24 “Anti-No-Flow Detection Time” by
increments of 5 seconds. Repeat Step 3 each time P2-24 is adjusted.

Step 4: Create a no-flow situation (e.g. close discharge valve). Use monitor U1-99 “ANF Timer” to verify the value is increments
and holds at the P2-24 time (value set in Step 3). Once the Anti-No-Flow timer expires, the speed will reduce gradually until
reaching minimum pump speed (P1-06) where it will hold for 5 seconds according to P2-03, before going to sleep.

Step 5: Operate the system in normal AUTO operation and verify sleep and wake-up functions satisfactory.

(Parameters P2-23, P2-24, P2-25)

Step

10

HAND Mode Operation

Page 6 of 12

iQpump Micro AC Drive
Simplex Quick Start Procedure

Step

10

HAND Mode Operation (continued)