YASKAWA ELECTRIC TM.V1000SW.134A 1000 Hz High Frequency Custom Software Supplement
9
3 Modifications from Standard Software
3
Modifications from Standard Software
Changed Item
High Frequency Software
Standard Software
Applicable Drive Models
All
All
Maximum Output Frequency
1000 Hz (1167)
<1> In order to set the frequency reference above 1000 Hz, consult the Yaskawa Application Engineering group at
(800-927-5292) for application review and procedures.
400 Hz
Carrier Frequency
Max: 7 kHz
C6-02: 2, B, C, F
Max: 15 kHz
C6-02: 1 ~ A, F
Drive Current Rating
Fixed at Heavy Duty (HD) ratings
Depends on C6-01
Drive Overload Rating
Fixed at 150%/1 min. (C6-01 fixed)
Depends on C6-01
Control Mode
Fixed at V/f (A1-02 fixed)
V/f, OLV, OLV for PM
DriveWorksEZ (DWEZ)
No
Available
Communication Option Kits
No
Available
Frequency Setting Resolution
Fixed at 0.1 Hz
0.01 Hz (less than 100 Hz)
0.1 Hz (above 10 Hz)
Frequency reference and
output frequency display
units.
o1-03 parameter (same as b5-20)
0: 0.1 Hz
1: 0.01 (Max frequency 100%)
2: Deleted
3: User Defined (o1-10 and o1-11)
o1-03 parameter (same as b5-20)
0: 0.1 Hz
1: 0.01 (Max frequency 100%)
2: RPM
3: User Defined (o1-10 and o1-11)
<2> MEMOBUS/Modbus frequency reference can be set by 0.1 Hz. For 1000 Hz reference, 10000 (2710Hex) must be
set to 0002Hex MEMOBUS/Modbus register.
<3> Also applies to register data via MEMOBUS/Modbus RTU communication.
Torque Compensation
Enabled only at low speeds.
Refer to New and Modified Software
Functions on page 14
.
Constant throughout the entire
frequency range.
On-Delay Compensation
Enabled only at low speeds. Addition of On-
Delay Compensation Selection parameter S1-
01
Refer to New and Modified Software
Functions on page 14
.
Enabled throughout the entire
frequency range.
Stall Prevention Level During
Acceleration (L3-02)
Maximum setting: 170%
Maximum setting: 150%
Deleted Functions
• All OLV and OLV for PM specific
parameters
• All OLV and OLV for PM specific monitors
• Estimation type Speed Search
• High Slip Braking (HSB)
• Auto-Tuning
• KEB
• Overexcitation Deceleration
Refer to Modified Parameters on page 10
-