Installing the inverter

Operating Instructions Powador 12.0 TL3-20.0 TL3

Page 17

Authorised electrician

7.2.1 Connecting the inverter to the power grid

The power connection wires are connected on the right of the connection area (see Figure 6 on page 16).

DANGER

Risk of fatal injury due to electric shock
Severe injury or death will result if the live connections are touched.

Switch off all power sources to the inverter before you insert the grid power cable into the unit.

Make sure that the device is isolated from the public power supply and the system power supply

before starting work.

Recommended conductor cross-sections and fuse protection of NYM cables for fixed wiring according to

VDE 0100 part 430
For cable lengths up to 20m, use the specified conductor cross-sections. Longer cable lengths require larger

conductor cross-sections.

Model

Conductor cross-

section

Fuse protection: gL safety fuses or comparable

automatic circuit breakers

Powador 12.0 TL3

6.0 mm²

25 A for 4.0 mm² conductor cross-section

Powador 14.0 TL3

6.0 mm²

25 A for 4.0 mm² conductor cross-section

Powador 18.0 TL3

6.0 mm²

32 A for 6.0 mm² conductor cross-section

Powador 20.0 TL3

6.0 mm²

32 A for 6.0 mm² conductor cross-section

Table 2:

Recommended conductor cross-sections and fuse protection of NYM cables

NOTE
When the line resistance is high (i.e. long grid-side cables), the voltage at the grid terminals of the

inverter will increase during feed-in to the grid. The inverter monitors this voltage. If it exceeds the

country-specific grid overvoltage limit value, the inverter switches off.

Ensure that the conductor cross-sections are sufficiently large or that the cable lengths are

sufficiently short.

Making the grid connection

↻ Use cables with five wires (L1, L2, L3, N, PE).
1. Unscrew the cable fitting.
2. Remove the outer cladding of the AC cables.
3. Insert the AC leads through the cable fitting into the connection area.
4. Strip the insulation from the AC cables.
5. Open the locks for the PCB terminals.
6. Connect the cables in accordance with the label on the PCB terminals

(Figure 7 on page 17).

7. Close the locks for the PCB terminals.
8. Check that all connected cables are securely fitted.
9. Tighten the cable fitting.

PE N

BU

L2

BK

L1

BN

GNYE

L3

GY

»

The inverter is now connected to the power grid.

Figure 7: AC connection terminals

NOTE

An AC-side disconnection unit must be provided in the final installation. This disconnection unit

must be installed so that it can be accessed at any time without obstruction.
If a residual current circuit breaker is necessary due to the installation specification, a type B residual

current circuit breaker must be used.