Installing the inverter

Operating Instructions Powador 12.0 TL3-20.0 TL3

Page 21

Authorised electrician

7.2.2.4 Parallel input connection

The DC inputs can also be connected in parallel. Only strings with identical MPP voltage can be connected in

parallel (Un

1

=Un

2

=Un

m

).

The maximum permissible rated current (DC) doubles with parallel connection of both MPP trackers.
In case of a parallel input connection, MPP trackers A and B must be bridged. If input 1 is connected to input 2 and

input 3 is connected to input 4, then there is no parallel operation! The maximum rated current (DC) should also

be observed. Parallel operation is automatically recognized by the inverter.

Electrical data for parallel connection

Connecting the DC inputs

Number of modules per string: n

1

=n

2

=n

m

P

max

< max. recommended PV generator power

I

max

< 2 * max. rated current (DC)

1

A

B

2

3

4

U

MPP

...

n

1

n

2

n

m

=

=

Figure 10: Parallel input connection in

the generator junction box