Installing the inverter

Page 22

Operating Instructions Powador 12.0 TL3-20.0 TL3

Authorised electrician

7.2.2.5 Unconnected inputs

NOTE

If one of the MPP trackers (A or B) is not used, then it must be short-circuited, otherwise faults can

occur in the self-test of the unit and the feed-in operation is not guaranteed. The short-circuiting of

an MPP tracker does not result in the device being damaged.
The recommended standard connection or the parallel input connection should always be used as

a matter of course before an MPP tracker is short-circuited and therefore remains unused.

Electrical data for unused MPP trackers

Connecting the DC inputs

Number of modules per string: n

1

=n

2

=n

m

P

max

Per string < 0.5 * max. recommended PV generator power P

max

on the

MPP tracker used < max. power per tracker

I

max

< max. rated current (DC)

1

A

B

2

3

4

U

MPP

...

n

1

n

2

n

m

=

=

Figure 11: Parallel input with Y-adapter, short-circuits the unused MPP Tracker B