Maintenance/Troubleshooting

Operating Instructions Powador 12.0 TL3-20.0 TL3

Page 49

Status

Display

Explanation

Action

FS 17

Shutting down

Powador-protect

The activated grid and system

protection has been tripped.

"

Wait for reactivation.

"

Notify your

authorised

electrician if the fault

occurs several times.

E

FS 18

Resid. current

shutdown

Residual current was detected. The

feed-in was interrupted.

"

Notify your

authorised

electrician.

E

FS 19

Generator

insulation fault

There is an insulation fault on the PV

generator. The feed-in was interrupted.

"

Notify your

authorised

electrician if the fault

occurs several times.

E

FS 30

Voltage trans. fault

The current and voltage measurements

in the inverter are not within acceptable

range.

-

-

FS 32

Self test error

The internal grid separation relay test

has failed.

"

Notify your

authorised

electrician if the fault

occurs several times.

E

FS 33

DC feed-in error

The DC feed-in has exceeded the

permitted value. This DC feed-in can

be caused by grid conditions and may

not necessarily indicate a fault.

"

Notify your

authorised

electrician if the

fault occurs multiple

times.

E

FS 34

Internal

communication

error

A communication error has occurred

in the internal data transmission.

"

Notify your

authorised

electrician.

E

"

Check the data cable.

FS 35

Protection

shutdown SW

Protective shutdown of the software

(AC overvoltage, AC overcurrent,

DC link overvoltage, DC overvoltage,

DC overtemperature).

Not a fault Grid-related

shutdown, the grid connects

again automatically.

FS 36

Protection

shutdown HW

Protective shutdown of the hardware

(AC overvoltage, AC overcurrent,

DC link overvoltage).

Not a fault Grid-related

shutdown, the grid connects

again automatically.

FS 38

Generator

overvoltage error

The voltage of the DC generator

is too high. The PV generator is

configured incorrectly.

"

Notify your

authorised

electrician.

E

FS

41

42

Line failure:
Under voltage L1,

Over voltage L1,

The voltage of a grid phase is too low;

the grid cannot be fed into. The phase

experiencing failure is displayed.

"

Notify your

authorised

electrician.

E

43
44

Under voltage L2,

Over voltage L2,

45
46

Under voltage L3,

Over voltage L3,

FS 47

Grid failure: phase-

to-phase volt.

The measured line-to-line voltage is

outside of the tolerance limits.

Table 3:

Operating status and fault messages on the display