Configuration and Operation

Operating Instructions Powador 12.0 TL3-20.0 TL3

Page 39

Country-

spec. Setting

Menu

level

Display/settings

Action in this menu/meaning

0

1

2

3

1

Powador-protect

Configures the support for grid shutdown by a Powador

protect connected to the digital input of the inverter.

↻ For Auto/On: A Powador protect is operating in

the photovoltaic system and is connected to the

inverter at the digital input/output.

"

Auto: The inverter automatically detects a Powador-

protect integrated into the photovoltaic system.

"

On: The digital signal of the Powador protect must

be present to the digital input of the inverter for the

inverter to start with feed-in.

"

Off: The inverter does not check whether a Powador-

protect is integrated into the photovoltaic system.

0

1

2

3

1

Iso.resistor

"

Set threshold value (in 1 kOhm steps) at which the

insulation monitor reports a fault.

DE-MSp, FR,

AT, PL, RU,

ES, TH, ZA

0

1

2

3

1

Activate FRT

The inverter supports dynamic grid stabilisation

(Fault Ride-Through) in accordance with the BDEW

Medium Voltage Directive.

"

Specify constant k.

"

Specify the dead band.

"

Activate or deactivate FRT.

DE, BE, FR,

GB, IL, IT, AT,

PL, RU, ES,

KR, TH, ZA

0

1

2

3

1

Reactive power

"

Open the menu: Press the right arrow button or

the OK button.

"

Activating idle power process: select process and

press OK. The active process is highlighted.

0

1

2

3

2

cos-phi

specification

"

Configure power factor.

"

If a power factor not equal to 1 is selected: Select the

type of phase shift (under-excited/over-excited).

DE-MSp, FR,

GB, IL, IT, AT,

PL, RU, ES,

KR, TH

0

1

2

3

2

Q const.

"

Set the idle power Q (in %) to a fixed value.

"

Select the type of phase shift (under-excited/

over-excited).

DE, BE, GB, IT,

AT, ES, KR, UD

0

1

2

3

2

cos-phi(P/Pn)

"

Open the menu: Press the right arrow button or

the OK button.

GB, IT, AT, ES,

KR

0

1

2

3

3

Lock-in voltage

"

Power range set as % of rated voltage, where the

network support process is active.

0

1

2

3

3

Lock-out

voltage

DE, BE, FR,

GB, IL, IT, AT,

PL, RU, ES,

KR, TH, UD

0

1

2

3

3

Number of

nodes

This option defines how many support points can be

defined in the subsequent menu. The maximum number

of configurable support points depends on the selected

grid type.

"

Specify the number of support points for the idle

power characteristic curve.

0

1

2

3

3

1., 2. ...Support

point

"

Specify the power factor for the 1st, 2nd (etc.)

support point

"

If a power factor not equal to 0 is selected: Select the

type of phase shift (under-excited/over-excited).