Configuration and operation – KACO Powador 10.0 - 20.0 TL3 User Manual
Page 38

EN
EN
Configuration and Operation
Page 38
Operating Instructions Powador 12.0 TL3-20.0 TL3
Country-
spec. Setting
Menu
level
Display/settings
Action in this menu/meaning
DE, FR, GB,
HU, IL, IN, IT,
AT, PL, RU, ES,
TH, ZA, UD
0
1
2
3
1
Undervoltage
shutd.
"
Specify the shutdown threshold for fast and slow
overvoltage shutdown.
"
Set period from occurrence of the fault to shutdown
of the inverter.
DE, FR, GB,
IN, IT, AT, PL,
RU, ES, TH,
ZA, UD
0
1
2
3
1
Overfreq. shutd.
"
Set limit value for overfrequency shutdown.
0
1
2
3
1
Underfreq. shutd.
"
Set limit value for the underfrequency shutdown.
FR, IL, IN, IT,
AT, PL, RU,
TH, ZA, UD
0
1
2
3
1
Connection cond.
The inverter checks mains voltage and frequency.
The grid feed operation begins if the measured values
are within the set ranges.
"
Set minimum and maximum values for the
switching on.
DE, BE, FR,
GB, IL, IN, IT,
AT, PL, RU, ES,
TH, ZA, UD
0
1
2
3
1
Connect time
"
Set period for grid observation (in seconds) when
switching on and reconnection after a fault.
IL, IT, ZA
0
1
2
3
1
P(f) Gradient
"
Set gradient of power limit function with increasing
frequency in % / Hz. This percentage relates to the
nominal frequency of 50 Hz.
0
1
2
3
1
P(f) thresholds
"
Set the frequency thresholds for activating and
deactivating the power limitation in Hz.
0
1
2
3
1
DC starting volt.
The inverter begins feed-in as soon as this DC voltage
is present.
"
Set the starting voltage.
0
1
2
3
1
DC connection
"
Select between automatic detection and manual
setting.
"
Note the connection examples!
0
1
2
3
1
Const. volt. ctrl.
Lets you deactivate the MPP seek mode in order to
operate the inverter with a constant DC voltage.
"
Activate or deactivate function.
"
Set value for constant voltage control (200 – 800 V).
NOTE: For voltages below the minimal MPP voltage
the possible input power is reduced. The input current is
limited to 34 A per input.
0
1
2
3
1
Power limitation
The output power of the inverter can be set permanently
to a lower value than the maximum output power by the
internal power limiting. This may be necessary in order to
limit the maximum power rating of the system at the grid
connection point, upon the grid operator's request.
The value can be protected from the very first output
limitation entry. After setting a limitation, the value can
only be changed by entering a device-specific password.
1. Activate password protection if necessary.
2. Specify the activation status.
3. Specify the limit value for maximum feed-in power.
4. Confirm the entry with the OK button.