Configuration and operation – KACO Powador 10.0 - 20.0 TL3 User Manual

Page 38

Advertising
background image

EN

EN

Configuration and Operation

Page 38

Operating Instructions Powador 12.0 TL3-20.0 TL3

Country-

spec. Setting

Menu

level

Display/settings

Action in this menu/meaning

DE, FR, GB,

HU, IL, IN, IT,

AT, PL, RU, ES,

TH, ZA, UD

0

1

2

3

1

Undervoltage

shutd.

"

Specify the shutdown threshold for fast and slow

overvoltage shutdown.

"

Set period from occurrence of the fault to shutdown

of the inverter.

DE, FR, GB,

IN, IT, AT, PL,

RU, ES, TH,

ZA, UD

0

1

2

3

1

Overfreq. shutd.

"

Set limit value for overfrequency shutdown.

0

1

2

3

1

Underfreq. shutd.

"

Set limit value for the underfrequency shutdown.

FR, IL, IN, IT,

AT, PL, RU,

TH, ZA, UD

0

1

2

3

1

Connection cond.

The inverter checks mains voltage and frequency.

The grid feed operation begins if the measured values

are within the set ranges.

"

Set minimum and maximum values for the

switching on.

DE, BE, FR,

GB, IL, IN, IT,

AT, PL, RU, ES,

TH, ZA, UD

0

1

2

3

1

Connect time

"

Set period for grid observation (in seconds) when

switching on and reconnection after a fault.

IL, IT, ZA

0

1

2

3

1

P(f) Gradient

"

Set gradient of power limit function with increasing

frequency in % / Hz. This percentage relates to the

nominal frequency of 50 Hz.

0

1

2

3

1

P(f) thresholds

"

Set the frequency thresholds for activating and

deactivating the power limitation in Hz.

0

1

2

3

1

DC starting volt.

The inverter begins feed-in as soon as this DC voltage

is present.

"

Set the starting voltage.

0

1

2

3

1

DC connection

"

Select between automatic detection and manual

setting.

"

Note the connection examples!

0

1

2

3

1

Const. volt. ctrl.

Lets you deactivate the MPP seek mode in order to

operate the inverter with a constant DC voltage.

"

Activate or deactivate function.

"

Set value for constant voltage control (200 – 800 V).

NOTE: For voltages below the minimal MPP voltage

the possible input power is reduced. The input current is

limited to 34 A per input.

0

1

2

3

1

Power limitation

The output power of the inverter can be set permanently

to a lower value than the maximum output power by the

internal power limiting. This may be necessary in order to

limit the maximum power rating of the system at the grid

connection point, upon the grid operator's request.
The value can be protected from the very first output

limitation entry. After setting a limitation, the value can

only be changed by entering a device-specific password.
1. Activate password protection if necessary.
2. Specify the activation status.
3. Specify the limit value for maximum feed-in power.
4. Confirm the entry with the OK button.