3.2 Bypass Mode

The UPS automatically switches to Bypass mode if it detects an overload, load fault, or

internal failure. The bypass source supplies the commercial AC power to the load directly.

C A U T I O N

The critical load is not protected while the UPS is in Bypass mode.

Figure 3-2 shows the path of electrical power through the UPS system when the UPS is

operating in Bypass mode.

Bypass

Input

Rectifier

Input

Output

Path of electrical power

Battery

Rectifier

Inverter

Bypass

K4

Transformer

K3

(Open)

CB1

Figure 3-2. Path of Current Through the UPS in Bypass Mode

You can transfer the UPS from Normal mode to Bypass mode manually. However, the UPS

switches automatically to Bypass mode whenever the inverter can no longer supply the

critical load. If the UPS transfers to Bypass mode from Normal mode due to any reason

other than operator intervention, the UPS automatically attempts to transfer back to

Normal mode (up to three times within a 10-minute period). The fourth transfer will lock

the critical load on the bypass source and requires operator intervention to transfer.

Bypass mode is a normal operating mode, and not an alarm condition. However, if the UPS

is unable to return to Normal mode following an automatic transfer to Bypass mode, an

alarm condition is recorded.