EATON Powerware

®

9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

7.7 System Configuration

The System Configuration mode allows you to modify special functions in your UPS. These

functions include programming of building alarms, customizing building alarm messages,

adjusting the nominal output voltage, and scheduling battery tests. The menus provided

and their function are described in this section.

7.7.1 System Configuration Mode Main Menu

When the System Configuration mode is selected with a terminal attached, you are

prompted to enter the password for this mode:

Please Enter Password:

The default password is EXIDE1. You may modify this password using the change password

function in the following menu. When the valid password is entered, the main menu

appears:

Program Mode Main Menu

1. Program Building Alarms
2. Program Unit Name
3. Adjust Output Voltage
4. Change Password
5. Battery Test Setup
6. Modify Low Battery Time
7. Exit Program Mode
Enter Selection:

7.7.2 Program Building Alarms

This menu provides access to all the functions available in the system configuration mode.

If 1 is entered at the prompt, you can program the building alarm functions:

Program Building Alarms

1. Enable/Disable Default Functions
2. Customize Alarm Messages
3. Return to Main Menu
Enter Selection: