EATON Powerware

®

9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

Chapter 9

Product Specifications

The UPS systems are housed in freestanding, double-front cabinets with safety shields

behind the doors. The UPS systems are available in 50/60 Hz with various output power

ratings. Smaller models within a system may be upgraded in the field to larger models:

Table 9-1. Model Numbers

System

Models

Notes

Powerware 9315 300

225 and 300 kVA

60 Hz only

Powerware 9315 250

200 and 250 kVA

50/60 Hz (400V models only)

Powerware 9315 225

225 kVA

60 Hz only

Powerware 9315 200

200 kVA

50/60 Hz (400V models only)

The following sections detail the input, output, environmental, and battery specifications

for the UPS.

Table 9-2. System Input

Operating Input

Voltage

(Nominal +10/–15%)

480 Vac for operation from 408 Vac to 528 Vac (60 Hz only)

400 Vac for operation from 340 Vac to 440 Vac (50/60 Hz only)

600 Vac for operation from 510 Vac to 660 Vac (60 Hz only)

Operating Input

Frequency Range

3 Hz of nominal (50 Hz or 60 Hz)

Operating Input

Current

Battery Charge

125% of full load for overload + battery charge

Actual load + 25% of full load for battery charge with 0.8 pF

output units

115% of full load for overload + battery charge

Actual load + 15% of full load for battery charge with 0.9 pF

output units

Reduced for Generator

Adjustable, set to 102%

Input Current

Harmonic Content

10% THD at full load (with input filter option installed)

Power Walk-In

Adjustable 3–60 second rectifier ramp-up to full utility load

Power Factor

Minimum 0.95

Line Surges

6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4