6-2

EATON Powerware

®

9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

6.2 Summary Alarm Contacts

Two summary alarm contacts are provided as a standard feature on the UPS. The alarm

contacts (one notice and one alarm) are located inside the UPS on the customer interface

panel (see Figure 6-2).

NOTICE NO

NOTICE NC

COMMON

ALARM NO

ALARM NC

COMMON

10

11

12

13

14

15

TB2

Figure 6-2. Summary Alarm Contacts

You can specify that each contact be either normally closed (NC) or normally open (NO). If

the state of the contact changes from the state you specify as normal, an alarm is issued.

You can connect these contacts to equipment at your facility (such as a light or an alarm

bell) to let you know when an alarm is active on the UPS. This feature is useful if the UPS is

located in a remote area where the UPS alarm horn may not be heard immediately.

C A U T I O N

Contacts should not be operated in excess of 30 Vac or 42.4V peak AC or DC @ 1A maximum.